Electrochemical protection equipment
VOLTAGE CONVERTER FOR CATHODIC PROTECTION WITH INTERMEDIATE FREQUENCY CONVERSION «ENERGOMERA»
PNKZ-PPCH-M10 B series
TOR 3415-025-22136119-2009
Automatic converters for cathodic protection of inverter type and modular construction are designed for industrial application as efficient protection against electrochemical (soil) corrosion of underground metal constructions, communications, pipelines, oil stores, mounting armature and other similar objects in conditions of corrosive soil attacks at adverse impact of ground currents. Converters of built-in type for placement under cover of various types and in complete electric devices (placement category - 2).
Standard compliance
- Complies with GOST R 51164-98 “Steel pipe mains. General requirements for corrosion protection”.
- Complies with "General technical requirements to modular stations of cathodic protection. OAO GAZPROM".
- Produced under the manufacturer’s TOR: TOR 3415-025-22136119-2009.
- Certified: certificate of conformity N РОСС.RU.МЕ86.Н00573.
Application field
Enterprises of petroleum, gas, chemical, power and other industrial complexes that have a network of main and non-main pipelines of different purposes (gas, oil, products pipelines, etc), other underground metal pipelines and constructions including those which are situated in the zones of DC electrified rail transport (railways, tramways, etc).
Various organizations having underground metal communications and constructions in the soils with high corrosion activity.
Specifications
| Items | Values | |||
|---|---|---|---|---|
| Supply main | single-phase, AC current | |||
| Supply main voltage, V | from 150 to 264 | |||
| Supply main frequency, Hz | 50±3 | |||
| Nominal output active power, kW | 0,6 | 1,0 | 1,2 | 2,0 |
| Nominal output current, A | 12,5(6,3) | 20(10) | 25(12,5) | 40(20) |
| Nominal output voltage, V | 48(96) | |||
| Efficiency output in the nominal mode, not less than, % | 86 | |||
| Power factor in the nominal mode, not less than | 0,97 | |||
| Protection level | IP20 | |||
| Converter’s weight, kg | From 17 to 23 depending on the modification | |||
| Overall dimensions (length L* depth B * height H), mm | 461х483х276 | |||
Converters provide
- automatic maintenance of given total potential (with resistive component) on the protected construction (pipeline);
- automatic maintenance of given polarization potential (without resistive component) on the protected construction (pipeline);
- automatic maintenance of given output current;
- automatic maintenance of output voltage;
- information signals exchange with telemechanic systems, directly to the controlled station or via communication modem, is carried out via RS-485 external digital interface and MODBUS RTU exchange protocol.
MAINTENANCE CONDITIONS
- climatic modification – U;
- placement category – 2 (under cover of various types);
- ambient air temperature range: from -45°С to +45°С;
- relative humidity (at environment temperature +25°С): up to 98 %;
- I, II atmosphere types;
- converters placement – built-in;
- converters’ operating mode – long-term, continuous;
- cooling – by air, natural.